GAS-FIRED VENTEDGAS-FIRED VENTEDGAS-FIRED VENTEDGAS-FIRED VENTEDGAS-FIRED VENTED W W W W WALL FURNACEALL FURNACEALL FURNACEALL FURNACEALL FU
CAUTION: Label all wires prior to disconnection whenservicing controls. Wiring errors can cause improperand dangerous operation. Verify proper oper
A. This appliance has a pilot which must be lightedby hand. When lighting the pilot, follow these in-structions exactly.B. BEFORE LIGHTING smell all
PILOT ADJUSTMENTLocate the pilot adjustment screw on the valve. The pilotflame should surround at least the top 3/8” of the powerpile(pilot generator
BBSK INSTALLATION INSTRUCTIONSSTEP 1. Select left or right side of front panel for most convenient location of the temperature control knob. Remember
BBSK INSTALLATION INSTRUCTIONSPage 14SIDE VIEWS / FRONT PANEL20-1/2”LEFTSIDEVIEWRIGHTSIDEVIEWFIGURE 9BBSKCONTROLSWITCH40225SWITCHBRACKET40230HEATSHIEL
BBSK KIT LIGHTING INSTRUCTIONSFOR YOUR SAFETY READ BEFORE LIGHTINGA. This appliance has a pilot which must be lighted byhand. When lighting the pilot
Page 16MODEL WFF81-C OPTIONAL FAN KITINSTALLATION INSTRUCTIONSNOTE: This fan kit is to be installed after installation of wall furnace and with the
GroundWHITEBLACKL2 White115 VACL1 Black115 VACBLACKFAN SWITCH BLACKBLACK BLACKMOTORWHITEGREEN GROUND WIREL2WhiteL1Black115 VAC 60 HZ - Less than
40542-A REAR REGISTER KIT (Optional Accessory)INSTALLATION INSTRUCTIONS FOR GRAVITY VENTED WALL FURNACESSTEP 1. Cut hole within stud space behind hea
40542-A REAR REGISTER KIT - ContinuedINSTALLATION INSTRUCTIONS FOR GRAVITY VENTED WALL FURNACESPage 19INNER PANELFIGURE 15PlasterGroundFrameClosedPo
READ CAREFULLY BEFORE INSTALLING UNITThese installation instructions are a general guide, and do not supersede applicable local codes and ordinances.
TROUBLE SHOOTING CHART for qualified serviceman - MAIN BURNER SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION Flame too large 1. Defective operator secti
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION Burner won’t 1. Pilot flame too large or too small. 1. Re-adjust pilot flame using adjustment on turn o
SINGLE WALL FURNACEModel NumbersNat. L.P.W255F W256FW355F W356FDUAL WALL FURNACEModel NumbersNat. L.P.W505F W506FNOTICE: When ordering any component
HOW TO PROPERLY ORDER PARTS: In addition to part description and part number, please give model number, serial number, and type of gas used. Thisinf
IMPORTANT SAFETY BULLETIN ON YOUR GAS CONTROL AND PILOT LIGHTSYSTEM FOR HEATING EQUIPMENTWHAT YOU DON’T KNOW CAN HURT YOU.Your pilot light system has
LIMITED WARRANTYThe Louisville Tin & Stove Co. warrants to the original user the accompanying product for the period specified herein, provided sa
1”11”2”SAFETY RULESA) The wall furnace should be located near the center ofthe house for best heat distribution.B) Due to high temperatures, the appli
COMBUSTION AND VENTILATION AIRWhen installed, this gas appliance must be provided with fresh air for combustion, ventilation, and dilution of hotflue
ALL COMBUSTION AIR FROM OUTDOORSTHROUGH SINGLE COMBUSTION AIR OPENINGUL Listed Vent CapUL Listed Gas VentOpeningAlternateOpeningLocationFIGURE DALL CO
VENTINGThis appliance must be properly connected to a ventingsystem.Consult local ordinances governing venting. Install onlyUL listed type BW 4” oval
ROUGH-IN INSTRUCTIONSNOTE: Maximum wall thickness for a dualwall (W505, W506) installation is 5-3/8”.STEP 1. Attach the base plate (purchasedwith th
ROUGH-IN INSTRUCTIONSNOTE: For proper combustion, make sure units arelevel, front to back and side to side.FIGURE 1ROUGH-INDIMENSI
B-W VENTFIGURE 3Casing“Z BracketFront PanelFrontPanelDoorFIGURE 5CINSTALLATIONSTEP 6. To place furnace into position, graspfurnace and lift so furnace